6
Alarm Signals
Alarm Code
Alarm 
Sound Problem
Reset Options
E8
Constant 
buzzer
Cabinet Temperature Sensor Malfunction 
Alarm 
 
Cabinet temperature sensor has failed.
After replacing sensor, alarm will reset. 
 
During alarm, press "RESET" to silence 
buzzer for 5 minutes.
E9
Constant 
buzzer
Defrost Temperature Sensor Malfunction 
Alarm
 
Defrost temperature sensor has failed.
After replacing sensor, alarm will reset. 
 
During alarm, press "RESET" to silence 
buzzer for 5 minutes.
E10
[Duel Temp 
Models Only]
10 beeps 
every ten 
seconds
Communication Alarm
Freezer and refrigerator boards not 
communicating properly to control 
compressor delay.
When communication is restored, alarm will 
reset. 
During alarm, press "RESET" to silence 
buzzer for 18 hours.
CF
1 beep 
every ten 
seconds
Clogged Filter Alarm 
Condenser filter needs cleaning.
Clean filter. Allow time for sensor to react, 
then press "RESET." 
During alarm, press "RESET" to silence 
buzzer for  hours. 
If this alarm occurs frequently, discharge 
temperature is consistently too high. 
Failure to take action could result in 
damage to the compressor.
door
[Except Glass 
Door Models]
 beeps 
every ten 
seconds
Display Only: Door open. 
Both Display and Beeps: Door open longer 
than 3 minutes.
Close door. During alarm, press "RESET" to 
silence buzzer for 3 minutes.
Note: Moving the diagnostic menu item 3 to "ON" resets all alarms regardless of 
whether or not the setpoints are reached. This is a complete clearing of all 
alarms. See "II.D.. Diagnostics Menu" for details.
F. Compressor Protector
When a combined temperature/amperage value is above the limit specified by the 
compressor manufacturer, a protector will operate independently, turning off the 
compressor. The compressor will restart when this protector has reset.
Note: 
1. Compressor protector resets automatically.
. If the condenser fan is operating and the compressor is off, it is most likely that the 
protector has operated.
G. Perimeter Frame Heater
This unit is equipped with a perimeter frame heater. This prevents the formation of 
condensate on the front frame of the unit under high humidity conditions. If operating the 
unit under conditions where condensate will not form, these heaters may be turned off 
using the switch on the control box.
H. Glass Door Heater
Glass door units are equipped with a door heater. This prevents the formation of 
condensate on the glass under high humidity conditions. If operating unit under 
conditions where condensate will not form, these heaters may be turned off using the 
switch on the control panel.