 Unit Installation
NetVanta 4305 Hardware Installation Guide
 42
Copyright © 2006 ADTRAN, Inc.
61200890L1-34H
Mounting Options
The NetVanta 4305 may be installed in a tabletop, wallmount, or 19-inch rackmount configuration. The 
following sections provide step-by-step instructions for rack mounting and wall mounting.
Rack Mounting NetVanta 4305
The NetVanta 4305 is housed in a 1U-high, rack-mountable chassis which can be installed into 19-inch 
equipment racks. Follow these steps to mount the NetVanta 4305 in a rack:
If you have purchased the VPN accelerator card, install it first. See Installing the 
NetVanta VPN Accelerator Card (P/N 1202368L1) 
on page 47
.
Instructions for Rack Mounting NetVanta
Step
Action
1
Position the NetVanta 4305 in a stationary equipment rack. This unit occupies 1U of space. To 
allow proper grounding, scrape the paint from the rack around the mounting holes where the 
NetVanta 4305 will be positioned.
2
Have an assistant hold the unit in position as you install two mounting bolts through the unit’s 
brackets and into the equipment rack using a #2 phillips-head screwdriver.
3
Proceed to the steps given in Supplying Power to the Unit on page 44.
Be careful not to compromise the stability of the equipment mounting rack when installing 
this product.