Table 5
NOTE
Required time for evacuation when capacity
of 100 liter/h vacuum pump is used
If tubing length is 
less than 10 m
10 min. or more
15 min. or more
If tubing length is 
more than 10 m
The required time in the above table is calculated 
based on the assumption that the ideal (or target) 
vacuum condition is around 10 mmHg abs.
(5)  With  the  vacuum  pump  still  running,  close  the 
“Lo”knob of the manifold valve. Then stop the 
vacuum pump.
(6)With  the  accessory  hex  wrench,  turn  the  valve 
stem  on  the  narrow  tube  service  valve 
counterclockwise by 90 degrees (1/4 turn) for 10 
seconds,  and  then  turn  the  stem  clockwise  to 
close it again. (Fig.40) 
(7)Leak test all joints at the tubing (both indoor 
and outdoors) with liquid soap. Bubbles indicate 
a  leak.  Be  sure  to  wipe  off  the  soap  with  a 
clean cloth.
(8)With the hex wrench, turn the wide tube service 
valve  stem  counter-clockwise  to  fully  open  the 
valve.
(9)Turn  the  narrow  tube  service  valve  stem 
counter-clockwise to fully  open the valve.
(10)Loosen  the  vacuum  hose  connected  to  the  wide 
tube  service  port  slightly  to  release  the 
pressure. Then, remove the hose.
(11)Replace  the  bonnet  and  flare  nut  on  the  wide 
tube  service  port  and  fasten  the  flare  nut 
securely with an adjustable wrench or box wrench. 
Next, mount the valve cap and tighten it with a 
torque  wrench  (the  cap  needs  to  be  tightened 
with  the  torque  of  200kg-cm).  This  process  is 
very  important  to  prevent  gas  from  leaking  from 
the system.
(12)Test run the air conditioner.
(13)While  the  air  conditioner  is  running,  apply 
liquid  soap  to  check  for  any  gas  leaks  around 
the service valves or caps.
(14)If  there  is  no  leakage,  stop  the  air 
conditioner.
(15)Wipe off the soap on the tubing.
            This  completes  air  purging  with  a  vacuum 
pump and    
              the  air  conditioner  is  ready  for  actual 
operation.
CAUTION
Be 
sure 
to 
completely 
insert 
the 
hex 
wrench 
before  attempting  to  turn 
Lo        
Hi
Indoor unit
Outdoor unit
Fig.39
Manifold valve
Pressure
gauge
Vacuum pump
90 (1/4 turn)
Narrow tube
Hex wrench
Wide tube
Valve cap
Vacuum hose to manifold valve
Fig.40