Electrical Requirements
If codes permit and a separate ground wire is used, it is 
recommended that a qualified electrical installer determine 
that the ground path and the wire gauge are in accordance 
with local codes.
Check with a qualified electrical installer if you are not 
sure the oven is properly grounded.
This oven must be connected to a grounded metal, 
permanent wiring system.
Be sure that the electrical connection and wire size are 
adequate and in conformance with the National Electrical 
Code, ANSI/NFPA 70 — latest edition or CSA Standards C22.  
1-94, Canadian Electrical Code, Part 1 and C22.2 No.  
O-M91 — latest edition, and all local codes and ordinances.
A copy of the above code standards can be obtained from:
National Fire Protection Association 
1 Batterymarch Park 
Quincy, MA 02169-7471
CSA International 
8501 East Pleasant Valley Road 
Cleveland, OH 44131-5575
Electrical Connection
To properly install your oven, you must determine the type 
of electrical connection you will be using and follow the  
instructions provided for it here.
 
Oven must be connected to the proper electrical voltage and 
frequency as specified on the model/serial/rating plate. The 
model/serial/rating plate is located under the control panel 
on single ovens and under the control panel on the upper 
oven cavity on double ovens. See the following illustrations.
A
A
Single Oven
A.  Model/serial/rating plate
Double Oven
A.  Model/serial/rating plate
 
Models rated from 7.3 to 9.6 kW at 240 volts (5.4 to 7.4 kW 
at 208 volts) require a separate 40-amp circuit. Models 
rated at 4.8 kW and below at 240 volts (3.6 kW and below 
at 208 volts) require a separate 20-amp circuit.
 
A circuit breaker is recommended.
 
Connect directly to the circuit breaker box (or fused 
disconnect) through flexible, armored, or nonmetallic 
sheathed, copper cable (with grounding wire). See the 
“Make Electrical Connection” section.
 
Flexible conduit from the oven should be connected 
directly to the junction box.
 
Fuse both sides of the line.
 
Do not cut the conduit. The length of conduit provided 
is for serviceability of the oven.
 
A UL Listed or CSA Approved conduit connector 
must be provided.
 
If the house has aluminum wiring, follow the 
procedure below:
1.  Connect a section of solid copper wire to the ends 
of the flexible conduit leads.
2.  Connect the aluminum wiring to the added section 
of copper wire, using special connectors and/or tools 
designed and UL Listed for joining copper to aluminum.
Follow the electrical connector manufacturer’s recommended 
procedure. Aluminum/copper connection must conform with 
local codes and industry accepted wiring practices.
For power requirements for models KOST107E, KOST100E, 
KOSE507E, KOSE500E, KODE307E, KODE300E, KODE507E, 
KODE500E, KODT100E, and KODT107E, refer to the following 
table.
Voltage Single 
Thermal
Single 
Convect
Double 
Thermal
Double 
Convect
Double 
Convect/
Thermal
240 VAC 4100 W
4100 W
8300 W
8300 W
8300 W
208 VAC 3100 W
3100 W
6300 W
6300 W
6300 W
240 VAC 17.2 A
17.2 A
34.2 A
34.2 A
34.2 A
208 VAC 15.0 A
15.0 A
29.9 A
29.9 A
29.9 A