Honeywell Bypass Flow Through Humidifier with Water Saving Technology (HE280) Guia Da Instalação

Página de 40
HE240, HE280 HUMIDIFIER AND INSTALLATION KIT
11
69-2686EF—01
d. Insert the tubing into the saddle valve fitting and support the valve while 
tightening the compression nut.
e. Insert plastic supply tubing into quick connect fitting. Insert fully, and apply 
modest pull pressure to ensure a tight fit.
4. Use the following steps to install a 
1/2 in. (13 mm) drain tube between the 
humidifier and the floor drain (see Fig. 10).
a. Slide the drain clamp over the tubing.
b. Push the tubing over the drain nipple 
on the humidifier.
c. Hand-tighten the clamp around the 
tubing to secure it to the humidifier 
drain. The clamp is tightened by com-
pressing the two sides together so 
that one side fits into the ridged grove 
on the other side.
d. Secure the tubing (can use foil tape) 
along the route to prevent movement 
and ensure downward slope for cor-
rect drainage.
Fig. 10. Installing the drain tubing.
NOTE: Cut tubing to correct length so the tubing terminates at the drain.
Connecting the Pressure Switch
1. If the humidifier is installed on 
the supply duct (as is recom-
mended), the pressure switch 
needs to have the tubing fed to 
the return duct. If the humidifier 
is installed on the return duct, 
the pressure switch needs to 
have the tubing fed to the supply 
duct.
2. Drill a 3/4-in. (19 mm) diameter 
hole in the duct within 10 ft. 
(3 m) of the switch to ensure the 
provided tubing reaches the 
pressure tap elbow.
Fig. 11. Pressure switch.
M20177
M33405
69-2686EF_A.book  Page 11  Friday, March 9, 2012  11:37 AM