Cisco Cisco ONS 15454 SDH Multiservice Provisioning Platform (MSPP) Guia Da Instalação

Página de 4
 
2
Installing the ONS 15454 SDH Air Ramp Rack Mounting Brackets
78-15834-01 June 2003
Related Documentation
19 in. or 23 in. ANSI racks as defined in ETS 300 119-1 (2,3,4)
19 in. ETSI racks as defined in ETS 300 119-1 (2,3,4)
Step 2
Align the mounting bracket screw holes against the shelf assembly screw holes according to 
. The bracket mounting holes will align with the forward-most mounting holes on the air ramp. 
When aligned properly the mounting flange will be 38 mm from the front edge of the air ramp.
Step 3
Insert the screws (2 places) as shown in 
 and tighten.
Step 4
Repeat for the other side of the assembly.
Figure 1
Positioning the mounting brackets
Refer to Cisco ONS 15454 SDH Procedure Guide for procedures to install the air ramp in a rack.
Related Documentation
Cisco ONS 15454 SDH Procedure Guide
Cisco ONS 15454 SDH Troubleshooting Guide
Cisco ONS 15454 SDH Reference Manual
Obtaining Documentation and Submitting a Service Request
For information on obtaining documentation, submitting a service request, and gathering additional 
information, see the monthly What’s New in Cisco Product Documentation, which also lists all new and 
revised Cisco technical documentation, at:
Subscribe to the What’s New in Cisco Product Documentation as an RSS feed and set content to be 
delivered directly to your desktop using a reader application. The RSS feeds are a free service. Cisco currently 
supports RSS Version 2.0.
Top View
Front
96688
Side View
38 mm
Screws 2 places