Cisco 5700 Series Wireless Controller Installation Guide
OL-28544-02
  Unpacking and Installing the Controller
Grounding the Chassis
Follow the grounding procedures at your site and observe these warnings:
Warning
This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the 
absence of a suitably installed ground conductor. Contact the appropriate electrical inspection 
authority or an electrician if you are uncertain that suitable grounding is available. 
Statement 1024
Warning
When installing or replacing the unit, the ground connection must always be made first and 
disconnected last. 
Statement 1046
Caution
We recommend grounding the chassis, even if the rack is already grounded.
Caution
All power supplies must be grounded. The receptacles of the AC power cables used to provide power to 
the chassis must be the grounding type, and the grounding conductors should connect to protective earth 
ground at the service equipment.
Note
The grounding lug must be NRTL listed and compatible with copper conductors. Only copper conductors 
(wires) must be used and the copper conductor must comply with National Electrical Code (NEC) for 
capacity. 
Follow these steps to install the grounding lug on the controller. Make sure to follow any grounding 
requirements at your site.
Step 1
Strip the ground wire to 0.5 inch (12.7 mm) ± 0.02 inch (0.5 mm) (see 
). Stripping more than 
the recommended amount of wire can leave exposed wire from the connector.
Figure 7
Stripping the Ground Wire
Step 2
Slide the open end of the ground lug over the exposed area of the wire.
Step 3
Using a Panduit crimping tool, crimp the ground lug to the wire.
Step 4
Remove the grounding bracket from the back of the controller by unscrewing the two Philips flat-head 
screws holding on the bracket (see 
Insulation
Wire lead
0.5 in. (12.7 mm) ± 0.02 in. (0.5 mm)
60528