Cisco Cisco ONS 15216 DWDM System Guia Da Instalação
13
Unpacking and Installing the Cisco ONS 15216 Three-Component Bay Assembly (15216-ILA-BAY)
78-16368-01
GMT Fuse and Alarm Panel
Figure 9
FAP Cabling
Figure 10
EDFA2 Power Cabling
GMT Fuse and Alarm Panel
The FAP included in the three-component bay assembly is a GMT FAP that includes a fuse panel and
low voltage disconnect (LVD). The LVD protects battery and network equipment life. If voltage to any
input power source falls below -39VDC, power is disconnected from the protected equipment. When
input voltage levels return to -47VDC, power is reestablished to the protective equipment.
low voltage disconnect (LVD). The LVD protects battery and network equipment life. If voltage to any
input power source falls below -39VDC, power is disconnected from the protected equipment. When
input voltage levels return to -47VDC, power is reestablished to the protective equipment.
shows the front view of the FAP and
Figure 11
GMT FAP (front view)
115004
115005
110995
LVD ALARM
B
POWER
B
FUSE
ALARM
6
7
8
9 10
1
2
3
4
5
WARNING!
DO NOT REMOVE MODULE BEFORE
DISCONNECTING POWER ON REAR
DISCONNECTING POWER ON REAR
LVD ALARM
A
POWER
A
FUSE
ALARM
6
7
8
9 10
1
2
3
4
5
WARNING!
DO NOT REMOVE MODULE BEFORE
DISCONNECTING POWER ON REAR
DISCONNECTING POWER ON REAR