Allen-Bradley devicenet modules in logix5000 control systems Manual Do Utilizador

Página de 239
Publication DNET-UM004A-EN-P - March 2004
Communicate with a PanelView™ Standard Terminal        9-13
Plan and Configure Explicit 
Server Tags
Explicit server tags are similar to I/O tags except that the controller 
initiates the communication with the terminal. Explicit server tags do 
not
 show up on the input and output maps of the scanner.
To configure an explicit server tag:
Assign Assembly Instances
Step:
See page:
Assembly 
Instance 
16
0
16 bits
1
16 bits
63
16 bits
Assembly 
Instance 
3
0
16 bits
1
16 bits
63
16 bits
Assembly 
Instance 
4
0
16 bits
1
16 bits
63
16 bits
Read Tag
Write Tag
A PanelView terminal gives you 14 assembly
instances (3 to 16) for explicit server tags.
Tag address = I:0
If a bit-level tag, then tag 
address = I:0/bit # (0 - 15)
Tag address = O:0
If a bit-level tag, then tag 
address = O:0/bit # (0 - 15)
Each instance give you 64 words for
either input or output data.
Write Tag
Use an assembly instance for either 
input (write) or output (read) tags, but 
not both.
Read Tag