Allen-Bradley devicenet modules in logix5000 control systems Manual Do Utilizador

Página de 239
Publication DNET-UM004A-EN-P - March 2004
9-16        Communicate with a PanelView™ Standard Terminal
Program the Controller to 
Get/Set Explicit Server Tags
To let the controller read/write data from/to an explicit server tag:
Create an Array for the Assembly Instance
For each assembly instance that you use for explicit server tags, create 
an array in the RSLogix 5000 project for the data.
Step:
See page:
Assembly 
Instance 
3
I:0
16 bits
I:1
16 bits
I:63
16 bits
Array_1[0]
Array_1[31]
Write Tags in PanelView
Array_2[0]
Array_2[31]
Controller Tags
Read Tags in PanelView
Controller Tags
Assembly 
Instance 
4
O:0
16 bits
O:1
16 bits
O:63 16 bits
Data type = DINT[32]
Data type = DINT[32]