Allen-Bradley devicenet modules in logix5000 control systems Manual Do Utilizador

Página de 239
Publication DNET-UM004A-EN-P - March 2004
Communicate with a PanelView™ Standard Terminal        9-19
Configure Explicit Client 
Tags
Use an explicit client tag to let the PanelView terminal get or set a 
parameter of another device on the DeviceNet network.
An explicit client tag:
• does not show up on the input or output map of the scanner
• does not involve the controller
• does not use an address in an assembly instance of the 
PanelView terminal
To configure an explicit client tag:
Determine the Parameter Number to Access
Use RSNetWorx software to determine the parameter number that you 
want to access:
 
Step:
See page:
Parameter
Parameter
Parameter
Read Tag
Read Tag
Write Tag
Device
PanelView Terminal
parameter number
means you can only get the value of the
parameter (read-only)
means you can only get the value of the
parameter (read-only)