Allen-Bradley devicenet modules in logix5000 control systems Manual Do Utilizador

Página de 239
Publication DNET-UM004A-EN-P - March 2004
Using POINT™ I/O Modules on a DeviceNet Network        15-3
Tally Memory 
Requirements
POINT I/O modules connect to an adapter or interface module. To 
tally their memory requirements:
POINT I/O 1734-ADN or 1734-ADNX Adapter
The ADN/ADNX adapter creates a small network (subnet) out of the 
modules and devices that are connected to it. You can configure the 
adapter to give each device on the subnet its own DINT or DINTs, 
which works best for a Logix5000 system.
To tally the memory requirements for POINT I/O:
For this module:
See page:
P
T
I/
O
P
T
I/
O
A
D
N
subnet
4
Device
Input Size of 
Device
(bytes)
Input Memory 
in Scanner 
(DINTs)
Output Size of 
Device
(bytes)
Output Memory 
in Scanner 
(DINTs)
Point I/O adapter-ADN
2
1
2
1
Point I/O input-IE2C
6
2
0
0
Point  I/O  output-OB4E
1
1
1
1
Total
4
2
Device
Address
Input Size of 
Device
(bytes)
Input Memory 
in Scanner 
(DINTs)
Output Size 
of Device
(bytes)
Output Memory 
in Scanner 
(DINTs)
start/stop buttons
1
1
1
1
motor starter
4
1
4
1
POINT I/O adapter w/ modules
4
2
1. Determine how many bytes each device sends and/or gets to/from your control system.
The adapter itself sends 2 bytes and gets 2 bytes.
2. Convert the input and output sizes to DINTs in the scanner.
3. Add the totals to the main tally.
sub-tally
main tally