Publication DNET-UM004A-EN-P - March 2004
Using POINT™ I/O Modules on a DeviceNet Network        15-13
If You Change the 
Configuration of the 
Adapter
Before you make an online change to a POINT I/O adapter 
1734-ADN/1734-ADNX that effects the size of its input or output data, 
remove the adapter from the scan list of the scanner. Otherwise, 
RSNetWorx software responds with the following error: Device state 
conflict.
For example, adding or removing an I/O module to/from the adapter 
changes the I/O data of the adapter. To add or remove a module:
1. Remove the adapter from the scan list of the scanner.
2. Add or remove the I/O module to/from the adapter and 
reconfigure the adapter.
3. Add the adapter back into the scan list.
Typically, changes that do not effect the I/O size are permitted while 
the adapter is still in the scan list. 
Interpret the Status 
Indicators
POINT I/O Interface 1734-PDN
System Power indicator
DeviceNet Power indicator
For this device:
See page:
State
Description
off
Either:
• DeviceNet power is off, or
• dc-dc converter problem.
green
• System power is on.
• dc-dc converter is active (5V).
State:
Probable Cause:
off
DeviceNet power is off.
green
Power on, 24V present