Allen-Bradley devicenet modules in logix5000 control systems Manual Do Utilizador
Publication DNET-UM004A-EN-P - March 2004
4-2 Automatically Configure a DeviceNet Network
How AutoScan Effects Your
Network
Network
As you use AutoScan, keep the following in mind:
Install the Node
Commissioning Tool
Commissioning Tool
Use this tool to set the DeviceNet address of a device that has no
switch, pushbutton, or other mechanism for its address.
switch, pushbutton, or other mechanism for its address.
If all your devices have a switch or pushbutton for their address, then
skip this step. You do not need the Node Commissioning tool.
skip this step. You do not need the Node Commissioning tool.
To install the Node Commissioning tool:
1. Get your RSLogix 5000 software CD.
2. On the CD, find the following folder:
language
\Tools\Node Commissioning Tool
where:
language
is the language of your software. For example, for
software in English, open the ENU folder.
3. Follow the instructions in the readmefirst file.
Consideration:
Description:
1. AutoScan clears the current
configuration.
With AutoScan, the scanner automatically sets up communication with the devices on your
DeviceNet network. When you turn on the AutoScan option, the scanner removes any
previous configuration that was done to the scanner.
DeviceNet network. When you turn on the AutoScan option, the scanner removes any
previous configuration that was done to the scanner.
2. AutoScan allocates a fixed memory
size for each device.
At its default setting, AutoScan allocates 1 DINT of input memory and 1 DINT of output
memory for each device on the DeviceNet network.
memory for each device on the DeviceNet network.
3. New devices are automatically
available.
While the scanner is in idle mode, AutoScan continues to establish communication with
devices that you connect to the network (as long as the device uses
devices that you connect to the network (as long as the device uses
≤ 4 bytes of input data
and
≤ 4 bytes of output data).
4. The Automatic Device Recovery
(ADR) option is not available.
To use the Automatic Device Recovery (ADR) option of a DeviceNet scanner, you have to
use RSNetWorx software to edit the configuration of the scanner. This turns off AutoScan.
use RSNetWorx software to edit the configuration of the scanner. This turns off AutoScan.
DINT
Input Memory
0
device at address 0
1
device at address 1
2
device at address 2
The actual data for the device fills the portion
that it needs and the rest remains unused.