Allen-Bradley devicenet modules in logix5000 control systems Manual Do Utilizador

Página de 239
1
Publication DNET-UM004A-EN-P - March 2004
Chapter
 4
Automatically Configure a DeviceNet 
Network
How To Use This Chapter
This chapter provides a quick method for configuring a DeviceNet 
network. It uses the AutoScan feature to establish communication 
between the controller and your devices with minimal steps.
To use the AutoScan feature to configure your network:
Determine If You Can Use 
AutoScan
To use this chapter, make sure your network meets the following 
requirements:
If your network does not meet the requirements listed above, then use 
chapters 5 to 7 to configure your network and control your devices.
Before you use this chapter:
Connect your computer to the 
system. See chapter 4.
Step:
Page:
Each device on your DeviceNet network (except the scanner):
• sends ≤ 4 bytes of input data
• gets ≤ 4 bytes of output data
You have one of the following DeviceNet scanners:
• ControlLogix 1756-DNB
• FlexLogix 1788-DNBO
Your scanner has the following firmware revision:
This scanner:
Requires this firmware:
ControlLogix 1756-DNB
revision 5.0 or greater
FlexLogix 1788-DNBO
revision 3.0 or greater