Allen-Bradley devicenet modules in logix5000 control systems Manual Do Utilizador

Página de 239
Publication DNET-UM004A-EN-P - March 2004
5-4        Connect Each Device to the Network
Procedures for Specific 
Devices
The following sections show how to set the address of specific 
devices.
ControlLogix Scanner 1756-DNB
CompactLogix Scanner 1769-SDN
For this device:
See page:
DeviceNet
TM
MOD/NET   I/O          OK
1. Connect the device to the network. (If disconnected or the network power is off, the 
pushbutton changes the baud rate.)
2. Turn on the power to the device.
3. Press and hold the manual configuration pushbutton until the device displays the desired 
address.
When you release the button, the device resets to the new address.
4. After the device resets, check the 4-character display on the front of the module:
If:
Then the:
A#address
address is OK
Duplicate Node Address
address conflicts with another device
The 1769-SDN device has no hardware mechanism to set its address.
1. Connect the device to the network.
2. Turn on the power to the device.
4. After the device resets, check the 2-character display on the front of the device. It shows 
the status code and address of the device (status code first, then address).