HDU-409 Lists 1, 2, and 3
April 30, 2003
 9
G
ENERIC
 I
NFORMATION
This section provides generic information for both the HiGain and PG-Flex 
applications.
D
OUBLER
 E
NCLOSURE
 C
APACITIES
 
WITH
 F
ULL
 
S
OLAR
 L
OAD
The physical location of the doublers is driven by the following three 
deployment rules:
1
Place the enclosures at the electrical limits (35 dB) of each span. This 
places the first doubler at the 35 dB location and the second at 70 dB and 
so on. This allows the maximum circuit range to be realized.
2
If Rule 1 is not applicable, try to make all spans the same electrical length 
(same 196 kHz loss). This minimizes the maximum span loss and assures 
maximum operating margin, resulting in optimal transmission 
performance on the HDSL cable pairs. If specific application constraints 
preclude using rule 2 or, if two different circuit layout choices have the 
same maximum span loss, then use Rule 3.
Caution must be observed when pushing doubler spans to 
their 35 dB maximum range. Refer to ADC’s Technical 
Advisory #TA-015 on HiGain operating ranges and general 
deployment guidelines.