The maximum recommended ambient operating temperature (TMRA) for most 
server products is 35°C (95°F). The temperature in the room where the rack is 
located must not exceed 35°C (95°F). 
  CAUTION:  To reduce the risk of damage to the equipment when 
installing third-party options: 
 
Do not permit optional equipment to impede airflow around the 
server or to increase the internal rack temperature beyond the 
maximum allowable limits. 
 
Do not exceed the manufacturer’s TMRA. 
 
Power requirements 
Installation of this equipment must comply with local and regional electrical 
regulations governing the installation of information technology equipment by 
licensed electricians. This equipment is designed to operate in installations 
covered by NFPA 70, 1999 Edition (National Electric Code) and NFPA-75, 1992 
(code for Protection of Electronic Computer/Data Processing Equipment). For 
electrical power ratings on options, refer to the product rating label or the user 
documentation supplied with that option. 
  WARNING:  To reduce the risk of personal injury, fire, or 
damage to the equipment, do not overload the AC supply branch 
circuit that provides power to the rack. Consult the electrical 
authority having jurisdiction over wiring and installation 
requirements of your facility.
 
  CAUTION:  Protect the server from power fluctuations and 
temporary interruptions with a regulating uninterruptible power supply 
(UPS). This device protects the hardware from damage caused by 
power surges and voltage spikes and keeps the system in operation 
during a power failure. 
When installing more than one server, you may need to use additional power 
distribution devices to safely provide power to all devices. Observe the following 
guidelines: 
  Balance the server power load between available AC supply branch circuits. 
  Do not allow the overall system AC current load to exceed 80 percent of the 
branch circuit AC current rating. 
  Do not use common power outlet strips for this equipment.