3.  Group read and write registers together in the programmable pointer list 
and access them with separate Modbus commands. The ETH-100 can 
process read requests and write requests faster when they are grouped together 
rather than the master having to issue multiple transactions to access disjoint 
registers.  This is especially true when the registers to be accessed are also 
configured as ASD scan registers.  Pointer registers can be accessed in any 
combination of starting register and length.  In the setup below, you would 
optimize ETH-100 efficiency by having two Modbus transactions: one read 
request with a length of 6 starting at register FC00, and one write request with a 
length of 2 starting at register FC08. 
 
Table 5: Grouping Read and Write Registers In The PPR List 
Modbus Pointer Registers 
(Also configured to be ASD READ 
scan registers) 
Modbus Pointer Registers 
(Also configured to be ASD 
WRITE scan registers) 
Register 
Points To… 
Register 
Points To… 
FC00 FE03 
FC08 FA02 
FC01 FE06 
FC09 FA01 
FC02 FD01 
FC0A   
FC03 FE02 
FC0B   
FC04 FC91 
FC0C   
FC05 FE04 
FC0D   
FC06  
FC0E  
FC07  
FC0F