10.9  Exceptions and Troubleshooting 
Although by no means exhaustive, Table 6 provides some possible causes behind 
some of the most common errors experienced when using the Modbus TCP/IP 
interface. 
 
Table 6: Troubleshooting Reference 
Problem Possible 
Cause 
Register addressing is off by 1 
Refer to Section 10.3 for Modbus/drive mapping 
Modbus TCP/IP client cannot establish 
communication with the ETH-100 
• 
Ensure at least one of the connected drives is powered on 
• 
Check that the drive and Ethernet communication cables 
are fully seated into their respective communication ports 
• 
Check the Ethernet communication parameters (IP 
address, etc.) 
Drive does not respond to network 
commands / frequency command 
• 
Check drive’s frequency mode and command mode 
selection parameters 
• 
Where applicable, confirm the values of bits #14 and #15 
of communication command word 
• 
Confirm that communication frequency command value is 
between lower limit and upper limit frequencies 
ILLEGAL FUNCTION exception 
(Modbus exception code 01) 
The indicated Modbus function is not supported: refer to section 
10.2 for a list of supported functions 
ILLEGAL DATA ADDRESS exception 
(Modbus exception code 02) 
The targeted drive register (or one in a group of targeted 
registers) does not exist: check the drive’s supported register 
list 
ILLEGAL DATA VALUE exception 
(Modbus exception code 03) 
The value written was rejected by the drive as invalid: check the 
value and drive setting range 
NEGATIVE ACKNOWLEDGE exception 
(Modbus exception code 07) 
• 
An attempt was made to write to a drive register while the 
drive was running that does not accept writes while the 
drive is running 
• 
An attempt was made to write to a read-only register 
• 
Confirm that the drive communication cable is fully seated 
into the drive’s and ETH-100’s communication ports 
• 
Confirm that the drive communication cable is not routed 
near the drive’s input power or motor wiring or any other 
electrical noise-producing cables or equipment 
GATEWAY PATH UNAVAILABLE 
exception (Modbus exception code 0A) 
Unit Identifier (UI) was invalid: UI must be 1 
 3 
GATEWAY TARGET DEVICE FAILED TO 
RESPOND exception 
(Modbus exception code 0B) 
The targeted drive is not online or failed to respond: 
• 
Confirm that the targeted drive is powered-on 
• 
Confirm that the drive communication cable is fully seated 
into the drive’s and ETH-100’s communication ports 
• 
Confirm that the drive communication cable is not routed 
near the drive’s input power or motor wiring or any other 
electrical noise-producing cables or equipment