Programming
Maintenance Programming Level
124
MS-9200UDLS   PN 52750:A    11/04/05
Pressing 3 while viewing Program Check screen will cause a screen similar to the 
following to be displayed:
The Zone No Output feature allows the programmer to view the zones which have not 
been programmed to at least one output device (not including general alarm Zone 00). 
The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have 
been programmed to an addressable detector with an address of 001 on loop 1 but have 
not been programmed to any output devices.  Use the up and down arrow keys to view 
all the zones without output assignments.
3.7.4  Walktest 
To perform a walktest, press 1 while viewing Maintenance Screen #2.  The following 
screen will be displayed:
The operator can press 1 to perform a silent walktest or 2 to perform an audible 
walktest.  The display will read UNIT IN WALKTEST.  To end the Walktest, press the 
Esc (Escape) key.
Pressing 3 after the walktest has been completed, will allow the operator to view the 
results of the walktest.
3.7.5  System
To program the time and date into the control panel, press 2 while viewing Maintenance 
Screen #2.  The following display will appear:
   ZONES NO OUTPUT
05 07 09 10 11 1D001
    PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
     WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW RESULT
Walktest Screen   
     SYSTEMS
1=TIME/DATE
System Screen