Programming
Master Programming Level
80
MS-9200UDLS   PN 52750:A    11/04/05
detectors and 99 control/monitor modules.  Newer devices can be set to addresses 
higher than 99 but these addresses will not function with the MS-9200UDLS.  
Note that It is permissible to mix old and new devices on the same loop but the 
FACP must be set for CLIP mode when older devices are installed.
3.6.5  System Setup
System Setup allows the programmer to configure the following control panel features:
• Trouble Reminder: This feature, when enabled, provides an audible reminder that 
an alarm or trouble still exists on the FACP after the control panel has been 
silenced.  The control panel piezo sounder will pulse once every 15 seconds 
during an alarm and every two minutes during a trouble condition, after the 
Alarm Silence or Acknowledge key is pressed.  The piezo will continue to sound 
at these rates until the alarm or trouble condition is cleared.  If the trouble 
condition is not cleared within 24 hours, the panel will reactivate the trouble 
sounder and retransmit the trouble condition to the central station if connected.
• Banner: This option allows the user to change the top two lines of the LCD 
display from the factory default readout of HONEYWELL LIFE SAFETY to a 
user defined readout when the control panel is in Normal condition.
• Time-Date: This feature allows the programmer to set the time, display format 
(24 hr or 12 hr), date and daylight savings time feature into the FACP memory 
• Timers: This option allows the programmer to set the PAS (Positive Alarm 
Sequence) time delay, Pre-Signal time delay and Waterflow time delay.
• NACs: This feature allows the programmer to configure the control panel 
Notification Appliance Circuits for a variety of options, such as circuit type, 
silenceable/nonsilenceable, autosilence, coding, silence inhibit, zone assignment 
and enable/disable.
• Relays: This option allows programming of two onboard relays for activation by 
various control panel events, such as alarm, trouble, supervisory, etc.
• Canadian Option: This option allows the automatic programming of ionization 
smoke detector sensitivity thresholds to Canadian specifications.
• Waterflow Silenceable: This option provides the ability to silence any output 
circuit activated by a monitor module programmed as a waterflow type.
Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the 
following screens to be displayed: 
    PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOP
Programming Screen #2
    SYSTEM SETUP
1=TROUBLE REM    OFF
2=BANNER
3=TIME-DATE
System Setup Screen #1  
    SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2  
    SYSTEM SETUP
1=CANADIAN OPT.   OFF
2=WATERFLOW SIL.  NO
System Setup Screen #3