Notification Appliance Circuits
Installation
MS-9200UDLS   PN 52750:A    11/04/05
33
2.5.1  Configuring NACs
The Notification Appliance Circuits on the main circuit board are configured for Style 
Y (Class B) or Style Z (Class A) by properly orienting the NACKEY card in JP6 which 
is located at the top of the main circuit board near the NAC terminal blocks TB3 and 
TB4.  The default configuration is for Style Y (Class B).  Refer to Figure 2.7 for 
information on installing the NACKEY card.
2.5.2  Style Y (Class B) NAC Wiring
CLASS A
CL
ASS B
NACKEY -PCA
NA
CKE
Y -
PCA
Figure 2.7 NAC Configuration Using NACKEY
NACKEY Card
JP6
Top edge of MS-9200UDLS 
Main Circuit Board
• Style Z (Class A) - install NACKEY into JP6 with 
Class A pointing down toward circuit board as 
illustrated to the right.
• Style Y (Class B) - install NACKEY into JP6 with 
Class B pointing down toward circuit board .
NACKEY must be inserted with text side facing in 
toward center of main circuit board and key into key-
slot as illustrated to the right.  It is keyed to prevent 
incorrect insertion.
NACKEY card slot
JP6
TB3
TB4
92nac
key.c
dr
Key
Key-slot
B
+
B
+
B
-
B
-
1
1
-
+
+
+
+
+
+
+
+
+
+
+
+
B
+
B
-
B
+
B
-
3 3
2
2
4 4
Figure 2.8 NAC Style Y (Class B) Wiring
4 Style Y (Class B) Notification Appliance Circuits, supervised and power-limited - 4.7 k
Ω, ½ watt P/N:71252 UL listed
Polarized Bells
Polarized Bells
Polarized Horns
Polarized Horns
Polarized Strobes
Notification Appliance Circuit 
polarity shown in alarm state
Dummy Load all unused circuit
TB4
920
0na
cy.c
dr
Polarized Strobes
circuit number
NAC 1
NAC 3
NAC 4
NAC 2
TB3