UL Power-limited Wiring Requirements
Installation
MS-9200UDLS   PN 52750:A    11/04/05
35
2.7  UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the 
cabinet.  All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away 
from any nonpower-limited circuit wiring and nonpower-limited circuit wiring must 
enter and exit the cabinet through different knockouts and/or conduits.  A typical wiring 
diagram for the MS-9200UDLS is shown below.
Figure 2.11 Typical UL Power-limited Wiring Requirements
Power-limited Circuits
Power-limited Circuits
Nonpower-limited Circuits
Power-limited Circuits
Nonpower-limited 
Circuits
AC Power
Grounding Stud
92udulpw
.cdr
Nonpower-limited Circuits
To Batteries
maintain minimum 0.25” 
between power-limited 
and nonpower-limited 
circuits wiring
Ground Strap
*Ferrite Beads
*Ferrite Beads
Wrap wire around ferrite bead as shown. 
Close ferrite bead. 
*Ferrite Bead Installation
Per FCC requirements, ferrite beads are required for the DC Power Outputs, Remote Power Supply Sync, ACS Output and SLC Circuit.