Honeywell MS-9600UDLSE Manual Do Utilizador

Página de 208
136
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
Programming
Master Programming Level
3.6.11  Clear Program
Pressing 2 while viewing Programming Screen #4, will select the Clear Program option.  This will 
cause the LCD to display the following screens: 
Pressing 1, for Whole System while viewing the Clear Program Screen #1, will clear all general 
system programming options and all programmed addressable devices from the nonvolatile mem-
ory of the FACP.  This function is useful when the control panel is first installed, prior to autopro-
gramming.  Note that it is necessary to autoprogram after using the Clear Whole System function.
Pressing 2, for All Loops while viewing the Clear Program Screen #1, will clear all programming 
related to all SLC loops and connected addressable devices.
Pressing 3, for Loop 1 while viewing the Clear Program Screen #1, will clear only the program-
ming related to SLC Loop 1 and the connected addressable devices.
Pressing 1, for Loop 2 while viewing the Clear Program Screen #2, will clear only the program-
ming related to SLC Loop 2 and the connected addressable devices.
Before executing any of the Clear commands listed above, the control panel will provide a warning 
to the user by prompting with the following display: 
Pressing 1 will cause the control panel to carry out the selected clear option.  Pressing 2 will pre-
vent programming from being cleared. 
    PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
   CLEAR PROGRAM
1=WHOLE SYSTEM
2=ALL LOOPS
3=LOOP1
   CLEAR PROGRAM
1=LOOP2
Clear Program Screen #1
Clear Program Screen #2
      WARNING!
  SYSTEM CHANGE
     PROCEED?
1=YES           2=NO