MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
Programming
Maintenance Programming Level
Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be 
displayed:
The Zone No Output feature allows the programmer to view the zones which have not been pro-
grammed to at least one output device (not including general alarm Zone 00). The example in the 
preceding screen indicates that Zones 05, 07, 09, 10, and 11 have been programmed to an address-
able detector with an address of 001 on loop 1 but have not been programmed to any output 
devices.  Use the up and down arrow keys to view all the zones without output assignments.
3.7  Maintenance Programming Level
To access Maintenance Programming mode, press the Enter key.  The LCD will display the follow-
ing: 
To enter the Maintenance Programming mode, press 2.  The display will read as follows: 
When the Maintenance level password (default 11111) is entered, the following screen will appear: 
   ZONES NO OUTPUT
05 07 09 10 11 1D001
1=READ STATUS
2=PROGRAMMING
3=REMOTE DOWNLOAD
PROGRAMMING
ENTER PASSWORD
    PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK