Programming
Master Programming Level
If the selected address has been added to programming and a detector (such as a photoelectric 
detector) with the selected address is physically installed on the SLC and is communicating with 
the control panel, the following will be displayed:
To change the programming for the displayed detector, press the keyboard ‘down’ arrow key to 
view the Edit Detector screens. 
 
In the preceding example:
• Normal - indicates that the detector with the selected address is physically installed on the 
SLC and communicating with the control panel (enabled)
• <ADJ><NOUN> - represents the adjective and noun, which have been programmed, 
describing the location of the displayed device
• ZNNN - represents the first of five possible software zones that the detector is assigned to 
(NNN = the three digit zone number from 000 - 099)
• V or * - indicates whether or not alarm verification is enabled (V = alarm verification 
enabled and * = alarm verification disabled)
• 1D017 - represents the Loop, Device type and Device address (1 = SLC Loop 1, D=Detector 
and 017 = Detector Address 017)
 NORMAL SMOKE (PHOTO)
 *********************
                ZNNN
             V  1D017
Edit Detector Screen #1