Honeywell MS-9600UDLSE Manual Do Utilizador

Página de 208
72
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
Programming
Master Programming Level
Pressing the down arrow key will display additional detector types as indicated in the following 
table: 
While viewing any Detector Type screen, select the type of detector being programmed by pressing 
the corresponding keyboard number key.  The display will return to Edit Detector Screen #2 and 
indicate the selection next to the Type option.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and 
not a false alarm.  This feature is selected by pressing 3 while viewing the Edit Detector Screen #2 
so that the display reads Verification On.  Each time the 3 key is pressed, the display will toggle 
between Verification On and Verification Off.  For a detailed description, refer to “Alarm Verifica-
tion” on page 159.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually 
resetting the control panel after each device activation.  To enable a device for the Walktest feature, 
press 1 while viewing the Edit Detector Screen #3 until the display reads Walktest Yes.  Each press 
of the 1 key will cause the display to toggle between Walktest Yes and Walktest No.  Refer to “Walk-
test” on page 160.
PAS
The PAS (Positive Alarm Sequence) option will program the detector to delay panel activation 
(including alarm relay and communicator) for a period of 15 seconds plus a programmable time of 
up to 3 minutes. Zone 97, however, will activate immediately and may be used to connect a signal-
ing device to indicate PAS activation (do not use a Notification Appliance Circuit for this purpose).  
To enable the PAS feature, press 2 while viewing the Edit Detector Screen #3 until the display reads 
PAS Yes.  Each press of the 2 key will cause the display to toggle between PAS Yes and PAS No.  
Refer to “Positive Alarm Sequence” on page 158.
For example, if a detector with address 005 is to be configured for PAS operation: 
• Select PAS Yes when editing the detector set to address 005  
Detector Type
Action When Activated
Smoke Photo
Fire Alarm
User-Defined-1
same as previous (Smoke Photo)
Smoke Ion
Fire Alarm
User-Defined-2
same as previous (Smoke Ion)
Heat Detect
Fire Alarm
User-Defined-3
same as previous (Heat Detect)
Smoke DuctP
Fire Alarm
User-Defined-4
same as previous (Smoke DuctP)
Photo w/Heat
Fire Alarm
User-Defined-5
same as previous (Photo w/Heat)
Duct-Superv
Supervisory, latching
User-Defined-6
same as previous (Superv DuctP)
Photo-SupervAR
Supervisory, nonlatching (works only in LiteSpeed)
User-Defined-7
same as previous (Photo-SupervAR)
ADAPT
Fire Alarm
User-Defined-8
same as previous (ADAPT)
Beam
Fire Alarm
User-Defined-9
same as previous (Beam)
NOTE: If a detector is selected as a SUPERV DUCTP type, it will function like a supervisory point, 
not a fire alarm point.  The supervisory LED and supervisory relay will activate, not the fire alarm LED 
or alarm relay, if smoke is sensed.
EDIT DETECTOR
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3