MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
99
Master Programming Level
Programming
Zones Available
Pressing 2 while viewing Zone Setup Screen #3 will display the following screen: 
The display will show all of the zones that are still available for programming.  Note that an up 
and/or down arrow may appear in the upper right corner of the display, indicating that additional 
screens of zone information exists.  Press the up or down arrow key to view additional screens.
3.6.4  Loop Setup
Loop Setup allows the programmer to configure the SLC Loop(s) for NFPA Style 4, 6 or 7 wiring 
and to select the protocol for each loop.  Pressing 1 while viewing Programming Screen #2 will 
cause the following screen to be displayed:
Loop Selection
Press 1 while viewing the Loop Selection Screen to configure Loop1 or 2 to configure Loop 2.  The 
following screens will appear for each loop.
Style
To program the SLC Style for the selected loop, press 1 for Style, while viewing Loop Setup 
Screen.  In the preceding example, the control panel is programmed for Style 4 SLC wiring as indi-
cated by the 4 to the right of Style in the display.  To change the wiring style, press 1 to toggle the 
display to read Style 6.  Each press of the 1 key will cause the display to toggle between Style 4 and 
Style 6.  Note that, when programming the Loop Style, the programmer can only select between 
Style 4 and Style 6.  To program a system for Style 7 wiring, the programmer must select the Loop 
Setup for Style 6.  Style 7 wiring is the same as Style 6 with the added requirement that each 
addressable device on the loop must have a pair of isolator modules, one on each side.
Note on SLC Troubles:  If the FACP reports an open fault on an SLC Loop programmed for Style 
6, the trouble condition will latch at the FACP.  When the SLC Loop has been repaired, the Reset 
button must be pressed at the FACP (at least 2 minutes after the trouble has been repaired) to clear 
the SLC trouble.
    ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Setup Screen #3
  ZONES AVAILABLE
01 02 03 04 05 06 07
08 09 10 11 12 13 14
15 16 17 18 19 
    PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOPS
Programming Screen #2
     LOOP SETUP
1=LOOP 1
2=LOOP 2
3-PROTOCOL    CLIP
Loop Selection Screen
     LOOP # SETUP
1=STYLE           4
Loop Setup Screen