Honeywell MS-9600LSE Manual Do Utilizador

Página de 208
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
13
Section 1: Product Description
The MS-9600LS and MS-9600UDLS are compact, cost effective, intelligent addressable FACPs 
(Fire Alarm Control Panels) with an extensive list of powerful features.  The combination of 
Fire•Lite’s newer series devices and legacy 300 Series devices, along with the MS-9600LS or MS-
9600UDLS FACP, offer the latest in fire protection technology.  The FLPS-7 power supply is a sep-
arate board while all other electronics are contained on a single main circuit board.  Both boards are 
mounted to a chassis and housed in a metal cabinet, providing a complete fire control system for 
most applications.  Optional modules, which plug into the main circuit board, are available for spe-
cial functions.  Available accessories include LED, graphic and LCD annunciators, reverse polar-
ity/city box transmitter, digital alarm communicator/transmitter, SLC expansion module, local and 
remote upload/download software and remote power expansion.  
The MS-9600UDLS includes a factory installed DACT-UD2 Digital Alarm Communicator Trans-
mitter.  Refer to “DACT-UD2 Installation” on page 52 and to the DACT-UD2 Manual Document 
#53037, which is supplied with the FACP, for DACT wiring and programming information.  The 
DACT transmits system status (alarm, troubles, AC loss, etc.) to a Central Station via the public 
switched telephone network.  It also allows remote programming or interrogation of the control 
panel using the PS-Tools Upload/Download utility via the public switched telephone network.  
Local programming and interrogation is also possible for the MS-9600UDLS using the PS-Tools 
and the USB port J4 on the DACT-UD2.  The MS-9600LS can be programmed and interrogated 
locally using the serial port at TB7.  Any personal computer with Windows® XP or greater and 
compatible modem with a speed of 2400 baud or faster and PS-Tools software may serve as a Ser-
vice Terminal.  This allows download of the entire program or upload of the entire program, history 
file, walktest data, current status and system voltages.
The MS-9600LSC is a ULC approved Canadian version of the FACP which offers the same fea-
tures as the MS-9600LS, but is supplied standard with a DP-9692 dress panel.  Refer to “Canadian 
Option” on page 113 
for a full description.
The MS-9600LSE and MS-9600UDLSE offer the same features as the MS-9600LS and MS-
9600UDLS but allow connection to 220/240 VAC input.
1.1  Inventory
When the FACP shipment is received, check to make certain that all parts have been included in the 
shipment.  The FACP shipment should consist of one of each of the following:
main circuit board with display
FLPS-7 Power Supply
chassis (with main circuit board and power supply mounted)
backbox with door and dress panel
plastic bag containing screws, cables, key, etc.
manual
1.2  Features and Options
New LiteSpeed™ polling protocol for faster SLC response time
SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire or 
3,000 ft (900 m) with untwisted, unshielded wire
Single standard addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
NOTE: Unless otherwise specified, the terms FACP, MS-9600LS and MS-9600UDLS are used 
in this manual to refer to all versions of the FACPs.