 SERIES B-VENT GAS FIREPLACES   •   36" LMBV MODELS   •   INSTALLATION INSTRUCTIONS
Typical Locations
See  Figure  1.  In  selecting  the  location,  the 
aesthetic and functional use of the appliance 
are primary concerns. However, vent system 
routing to the exterior and access to the fuel 
supply are also important. due to high tem-
peratures  the  appliance  should  be  located 
out  of  traffic  and  away  from  furniture  and 
draperies. Consideration should be given to 
traffic ways, furniture, draperies, etc., due to 
elevated  surface  temperatures.  The  location 
should also be free of electrical, plumbing or 
other heating/air conditioning ducting.
The appliance should be mounted on a fully 
supported  base  extending  the  full  width  and 
depth of the unit. The appliance may be located 
on or near conventional construction materials. 
However, if installed on combustible materials, 
such as carpeting, vinyl tile, etc., a metal or 
wood barrier covering the entire bottom surface 
must be used.
These  appliances  may  be  used  for  bedroom 
installations in the United States and are listed 
accordingly.  These units may not be installed 
in bedrooms in Canada.
Figure 1
LOCATION
Nominal operating pressures for the manifold 
side of the gas control system are; 3.5 inches 
water column (0.87 kPa) for natural gas models 
and  10  inches  water  column  (2.49  kPa)  for 
propane gas models.
These appliances are designed to operate on 
natural or propane gas only. The use of other 
fuels or combination of fuels will degrade the 
performance of this system and may be dan-
gerous.
Input of appliance is 24,000 bTU/HR.
  Gas 
Orifice  
  Type 
Size 
elevation
 
 
 
0 - 4500'
 
 
 
(0 - 1370 m)
 
 
 
0 - 4500'
 
 
 
(0 - 1370 m)
Natural
propane
(.058)
#42
(.0935)
Test  gage  connections  are  provided  on  the 
front of the millivolt gas control valve (iden-
tified  E  for  the  inlet  and  A  for  the  manifold 
side).    A  1/8"  NPT  test  gage  connection  is 
provided  at  the  inlet  and  manifold  side  of   
the electronic gas control valve.
Minimum inlet gas pressure to the appliance is 
4.5 inches water column (1.24 kPa) for natural 
gas and 11 inches water column (2.74 kPa) for 
propane for the purpose of input adjustment.
Maximum inlet gas supply pressure to the ap-
pliance is 10.5 inches water column (2.61 kPa) 
for natural gas and 13.0 inches water column 
(3.23 kPa) for propane.
The appliance must be isolated from the gas 
supply piping system (by closing its individual 
manual  shut-off  valve)  during  any  pressure 
testing  of  the  gas  supply  piping  system  at 
test pressures equal to or less than 1/2 psig 
(3.5 kPa).
The appliance and its individual shut-off valve 
must  be  disconnected  from  the  gas  supply 
piping system during any pressure testing of 
that system at pressures in excess of 1/2 psig 
(3.5 kPa).
These appliances must not be connected to a 
chimney or flue serving a separate solid fuel 
burning appliance.