Puls UC10.242 DIN-Rail UPS Guia De Especificação

Página de 27
 
 
UC10.241, UC10.242
 
 
UC-Series 
24V,
 
15A,
 
C
APACITOR
-
BASED 
B
UFFER 
M
ODULES
 
 
 
10.  E
FFICIENCY AND 
P
OWER 
L
OSSES
 
 
Efficiency  
typ. 
97.8% 
Normal mode, 10A output current, capacitor fully charged 
 
typ. 
97.8% 
Normal mode, 15A output current, capacitor fully charged 
Power losses 
typ. 
2.9W 
Normal mode, 0A output current, capacitor fully charged 
 
typ. 
4.6W 
Normal mode, 10A output current, capacitor fully charged 
 
typ. 
7.7W 
Normal mode, 15A output current, capacitor fully charged 
 
typ. 
5.0W 
During charging, 0A output current 
 
 
Fig. 10-1   Efficiency vs. output current in 
normal mode, typ. 
 
Fig. 10-2   Power losses vs. output current in 
normal mode, typ. 
Power losses versus output
current in normal mode
0
 
Efficiency vs. output
current in normal mode
94.5
0
7.5
2
5
15A
3
4
7
8W
Output Current
2.5
5
10
12.5
1
6
 
3
9
95.5
96.0
97.0
15A
95.0
96.5
97.5
98%
Output Current
5
7
11
13
 
 
 
 
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC) 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
11/27