Puls UC10.242 DIN-Rail UPS Guia De Especificação
UC10.241, UC10.242
UC-Series
24V,
15A,
C
APACITOR
-
BASED
B
UFFER
M
ODULES
9. PC-M
ODE
The PC-mode always turns the output off for at least 5s after a buffer event lasting longer than 1s, independent of
whether the 24V may have recovered during this time. This function ensures that the PC gets a restart signal. To
enable a safe shut-down of the system, the forced turn off of the output is delayed with a constant time of 70s.
whether the 24V may have recovered during this time. This function ensures that the PC gets a restart signal. To
enable a safe shut-down of the system, the forced turn off of the output is delayed with a constant time of 70s.
To activate the PC-mode, connect the two pins marked with “PC-mode” together on the signal connector together.
If the reset is to be controlled by the PC and not the buffer module, a wiring option called “external controlled
delayed shut-down” is available. See section 22.8 for details.
delayed shut-down” is available. See section 22.8 for details.
Fig. 9-1 PC-Mode -
Buffer event ends before buffer capacitors are discharged and buffer event is
shorter than 70s
>1s
Power Supply Output
Buffer Module Output
full
empty
Capacitor
Ready
Contact
Contact
closed
open
Buffering
Contact
Contact
closed
open
5s
70s
Example A:
The buffer event is longer than 1s
and ends before the buffer capacitors
are fully discharged.
After 70s of the beginning of the
buffer event, the output of the
buffer module will be switched off
for 5s.
The buffer event is longer than 1s
and ends before the buffer capacitors
are fully discharged.
After 70s of the beginning of the
buffer event, the output of the
buffer module will be switched off
for 5s.
Fig. 9-2 PC-Mode -
Buffer event discharges the buffer capacitors before the input recovers
Power Supply Output
Buffer Module Output
full
empty
Capacitor
Ready
Contact
Contact
closed
open
10/27
Buffering
Contact
Contact
closed
open
5s
Example B:
The buffer event lasts longer than the
buffer capacitors can supply the
output.
The buffer capacitors are fully
discharged before the input voltage
recovers.
The buffer module output will turn-
on earliest 5s after the power supply
output voltage has recovered.
The buffer event lasts longer than the
buffer capacitors can supply the
output.
The buffer capacitors are fully
discharged before the input voltage
recovers.
The buffer module output will turn-
on earliest 5s after the power supply
output voltage has recovered.
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC)
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany