Puls UC10.242 DIN-Rail UPS Guia De Especificação

Página de 27
 
 
UC10.241, UC10.242
 
 
UC-Series 
24V,
 
15A,
 
C
APACITOR
-
BASED 
B
UFFER 
M
ODULES
 
 
 
6.  B
UFFER 
T
IME
 
 
The following times are typical values for a new product and the aging effect during operation is not included. More 
information about the reduction of the buffer time over the life of the product can be found in the chapter 
“reliability”. 
 
 
UC10.241 
UC10.242 
 
Buffer Time 
typ. 
340s 
680s 
at 0.5A buffer current 
 
typ. 
200s 
400s 
at 1A buffer current 
 
typ. 
68s 
136s 
at 3A buffer current 
 
typ. 
39s 
78s 
at 5A buffer current 
 
typ. 
26s 
53s 
at 7A buffer current 
 
typ. 
16.5s 
33s 
at 10A buffer current 
 
typ. 
9s 
18s 
at 15A buffer current 
 
 
Fig. 6-1   Buffer time vs. buffer current, typ. 
 
 
 
Buffer Current
0
20
200s
40 60 80 100 120 140 160 180
Buffer Times
a
b
0
6A
4A
16A
8A
2A
10A
12A
14A
UC10.241
UC10.242
a
b
 
 
 
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC) 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
8/27