Puls UB10.241 UPS Guia De Especificação

Página de 23
 
 
 
UB10.241 
 
  USeries 
24V, 10A, DC-UPS 
 
 
 
20.  S
AFETY
 
 
  Output voltage  
SELV 
IEC/EN 60950-1  
   
PELV 
EN 60204-1, EN 50178, IEC 60364-4-41 
Max. allowed voltage between any input, output or signal pin and ground:  
60Vdc or 42.4Vac 
   
  Class of protection 
III 
PE (Protective Earth) connection is not required 
  Isolation resistance 
> 5MOhm 
Power port to housing, 500Vdc  
  Dielectric strength 
500Vac 
Power port to signal port 
   
500Vac 
Power port / signal port to housing 
Touch current (leakage current) 
The leakage current which is produced by the DC-UPS itself depends on the input 
voltage ripple and need to be investigated in the final application. 
17/23 
 
For a smooth DC input voltage, the produced leakage current is less than 100μA. 
 
 
21.  A
PPROVALS
 
 
 UL 
508 
LISTED   E198865   listed for use in U.S.A. (UL 508) and  
Canada (C22.2 No. 14-95) 
Industrial Control Equipment
 
IND. CONT. EQ.
18WM
 
 UL 
60950-1 
 
RECOGNIZED   E137006    recognized for the use in  
U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950)  
Information Technology Equipment, Level 5  
 
IEC 60950-1 
IECEE
 
CB SCHEME 
CB Scheme,  
Information Technology Equipment 
 
 
 UL 
1604 
RECOGNIZED   E246877    recognized for use in U.S.A. (UL 1604) and 
Canada (C22.2 No. 213-M1987) 
Hazardous Location Class I Div 2 T4 Groups A,B,C,D and  
Class I Zone 2 Groups IIA, IIB and IIC 
 
 
 
The unit is suitable for use in Class I Division 2 Groups A, B, C, D locations as well as for Class I 
Zone 2 Groups IIA, IIB and IIC locations. Substitution of components may impair suitability for 
Class I Division 2 environment. Do not disconnect equipment unless power has been switched 
off. Wiring must be in accordance with Class I, Division 2 wiring methods of the National 
Electrical Code, NFPA 70, and in accordance with other local or national codes. 
 
GL (Germanischer Lloyd) classified and ABS (American Bureau for 
Shipping) PDA for marine and offshore applications. 
 Marine 
GL
  
ABS
 
 
Environmental category: C, EMC2 
 
 
22.  F
ULFILLED 
S
TANDARDS
 
 
  EN/IEC 60204-1 
Safety of Electrical Equipment of Machines 
  EN/IEC 61131 
Programmable Controllers 
  EN 50178, IEC 62103 
Electronic Equipment in Power Installations 
June. 2010 / Rev. 1.3  DS-UB10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com   Phone +49 89 9278 0    Germany