Puls UB10.241 UPS Guia De Especificação

Página de 23
 
 
 
UB10.241 
 
  USeries 
24V, 10A, DC-UPS 
 
 
 
26.  A
CCESSORIES
 
 
Battery Modules 
Two pre-assembled battery modules with a single 12V battery are available for different buffer times. As an option, 
the mounting brackets are also available without batteries. This option offers more flexibility in selecting an 
appropriate battery or can save shipping and logistic costs. See individual datasheets for detailed information. 
 
 
 
UZK12.071 UZK12.261  
Battery type 
Standard version 
12V, 7Ah 
High current version 
12V, 26Ah 
VRLA lead-acid maintenance free 
battery  
 
  Service life 
3 to 5years 
10 to 12years 
According to EUROBAT guideline 
  Dimensions  
155x124x112mm 
214x179x158mm 
Width x height x depth 
 
Weight 
3.2kg 9.9kg  
 DIN-Rail 
mountable 
yes 
no 
 
 
Order 
number 
UZK12.071 UZK12.261 Battery 
module 
 
 
UZO12.07 UZO12.26 Mounting 
bracket 
without 
battery 
 
 
UZB12.071 UZB12.261 Replacement 
battery 
only 
 
 
Fig. 26-1   UZK12.071  
 
Fig. 26-2   UZK12.261 
20/23 
 
 
 
 
 
ZM1.WALL   Wall / Panel mounting bracket 
This bracket is used to mount the DC-UPS units onto a flat surface without utilizing a DIN-Rail. The two aluminum 
brackets and the black plastic slider of the DC-UPS have to be removed so that the two surface brackets can be 
mounted. 
Fig. 26-3   ZM1.WALL   Wall / Panel Mounting Bracket 
 
Fig. 26-4   Assembled Wall / Panel Mounting Bracket 
 
 
 
June. 2010 / Rev. 1.3  DS-UB10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com   Phone +49 89 9278 0    Germany