Example for calculating the service life and the required replacement cycle: 
Parameters for the example:  
ƒ 
A 7Ah battery with a design life of 3-5 years is used (e.g. Yuasa battery from the battery module UZK12.071) 
ƒ 
The average ambient temperature is 30°C 
ƒ 
One buffer event consumes approx. 25% of the achievable buffer time. 
ƒ 
One buffer event per day 
 
Calculation: 
Ambient temperature influence:  
According to Fig. 27-1 curve A, a 2
 
years service life can be expected for an ambient temperature of 30°C. 
Number of discharging cycles: 2 years * 365 cycles  = 730cycles in 2 years.  
According to Fig. 27-2, curve C has to be used (only 25% of battery capacity is required). 730 cycles have only a 
negligible influence in a battery degradation and can be ignored. 
Result: 
The battery shall be replaced after 2 years. 
Please note that the battery degrading begins from the production date (check date code on the battery) which may 
shorten the replacement intervals. 
 
Fig. 27-1   Service life versus ambient 
temperatures, typ *) 
Fig. 27-2   Cell capacity degradation vs. discharging 
cycles *) 
 
 
0
120%
100%
40%
20%
Number of Discharging Cycles
80
60%
80%
Cell Capacity
Depth of 
discharge 
A: 100% 
B:  50%
C:  30%
160
240
320
400
480
A
B
C
200
400
600
800
1000 1200
UZK12.261
UZK12.071
20°C
10
30°C
35°C
40°C 45°C
8
6
4
2
Ambient Temperature
25°C
1
3
5
7
9
Service Life in Years
Design Life
of Battery
A:  3-5 Years
B:  6-9 Years
C:  10-12 Years
A
B
C
22/23 
 
 
 
 
*) 
datasheet figures from battery manufacturer 
 
27.2.  P
ARALLEL AND 
S
ERIAL 
U
SE
 
Do not use the DC-UPS in parallel to increase the output power. However, two units of the DC-UPS can be paralleled 
for 1+1 redundancy to gain a higher system reliability. 
Do not use batteries in parallel, since the battery quality test might create an error message. 
Do not connect two or more units in series for higher output voltages. 
Do not connect two or more units in a row to get longer hold-up times. 