Puls UB10.241 UPS Guia De Especificação
UB10.241
U–Series
24V, 10A, DC-UPS
6. O
UTPUT IN
N
ORMAL
M
ODE
nom.
DC 24V
The output voltage follows the input voltage reduced by
the input to output voltage drop.
the input to output voltage drop.
Output voltage in normal mode
max.
0.3V
At 10A output current, see Fig. 6-1 for typical values
Voltage drop between input and
output
output
max.
0.45V
At 15A output current, see Fig. 6-1 for typical values
Ripple and noise voltage
max.
20mVpp
20Hz to 20MHz, 50Ohm *)
Output
current
nom. 15A
Continuously
allowed
Output power
nom. 360W
Continuously allowed
Short-circuit
current
min.
17.9A
Load impedance 100mOhm, see Fig. 6-2 for typical values
max.
21A
Load impedance 100mOhm, see Fig. 6-2 for typical values
4/23
Capacitive and inductive loads
No
limitation
*) This figure shows the ripple and noise voltage which is generated by the DC-UPS. The ripple and noise voltage
might be higher if the supplying source has a higher ripple and noise voltage.
Fig. 6-2 Output voltage vs. output current in
normal mode at 24V input, typ.
Fig. 6-1 Input to output voltage drop, typ.
Input to Output
Voltage drop
Voltage drop
0
0
2
10
0.1
0.15
0.25
18A
0.05
0.2
0.3
0.35
0.4V
Output Current
4
6
8
12 14 16
Output Voltage
0
0
5
10
15
20
4
8
12
28V
16
20
24
25A
Output Current
June. 2010 / Rev. 1.3 DS-UB10.241-EN
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
www.pulspower.com Phone +49 89 9278 0 Germany