Puls UB10.241 UPS Guia De Especificação

Página de 23
 
 
 
UB10.241 
 
  USeries 
24V, 10A, DC-UPS 
 
 
 
10.  E
FFICIENCY AND 
P
OWER 
L
OSSES
 
 
  Efficiency 
typ. 
97.8% 
Normal mode, 10A output current, battery fully charged 
  Power losses 
typ. 
2.9W 
Normal mode, 0A output current, battery fully charged 
   
typ. 
5.5W 
Normal mode, 10A output current, battery fully charged 
   
typ. 
5.0W 
During battery charging, 0A output current 
   
typ. 
18.5W 
Buffer mode, 10A output current 
 
 
Fig. 10-1   Efficiency at 24V, typ. 
 
Fig. 10-2   Losses at 24V, typ. 
Power losses versus output
current in normal mode
0
0
7.5
2
3
5
15A
1
4
6
7
8W
Output Current
2.5
5
10
12.5
Efficiency vs. output
current in normal mode
94.5
3
9
95.5
96.0
97.0
15A
95.0
96.5
97.5
98%
Output Current
5
7
11
13
9/23 
 
 
 
 
 
 
11.  F
UNCTIONAL 
D
IAGRAM
 
 
 
Fig. 11-1   Functional diagram 
DC-UPS Control Unit
Battery 
Charger
Battery 
Tester
Cut-off 
Relay
Battery
+
-
12V Battery
24V 
Power 
Supply
Input
-
+
-
+
Reverse 
Polarity 
Protection
Input Fuse
&
*
(5)
(6)
Ready 
Contact
(1)
(2)
Buffering 
Contact
(3)
(4)
Electronic
Current
Limiter
Buffered
Load
+
-
Output
Controller
Diagnosis LED (yellow)
Check Wiring LED (red)
Status LED (green)
Buffer-time Limiter
10s, 30s, 1m, 3m, 10m,
End-of-charge Voltage
Inhibit -
Inhibit +
Replace 
Battery 
Contact
Step-up 
Converter
(7)
(8)
 
 
*) 
Return current protection; This feature utilizes a Mosfet instead of a diode in order to minimize the voltage drop and power 
losses. 
June. 2010 / Rev. 1.3  DS-UB10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 