Puls UB10.241 UPS Guia De Especificação

Página de 23
 
 
 
UB10.241 
 
  USeries 
24V, 10A, DC-UPS 
 
 
 
9.  B
UFFER 
T
IME
 
 
The buffer time depends on the capacity and performance of the battery as well as the load current. The diagram 
below shows the typical buffer times of the standard battery modules. 
 
  Buffer time with battery module UZK12.071 
min. 
19’12’’ 
At 5A output current  *) 
   
min. 
5’42’’ 
At 10A output current  *) 
7/23 
   
typ. 
21’30’’ 
At 5A output current, see Fig. 9-1 **) 
   
typ. 
6’45’’ 
At 10A output current, see Fig. 9-1 **) 
  Buffer time with battery module UZK12.261 
min. 
99’30’’ 
At 5A output current  *) 
   
min. 
39’ 
At 10A output current  *) 
   
typ. 
130’ 
At 5A output current, see Fig. 9-1 **) 
   
typ. 
55’ 
At 10A output current, see Fig. 9-1 **) 
*)   Minimum value includes 20% aging of the battery and a cable length of 1.5m with a cross section of 2.5mm
2
 between the 
battery and the DC-UPS and requires a fully charged (min. 24h) battery. 
**)  Typical value includes 10% aging of the battery and a cable length of 0.3m with a cross section of 2.5mm
2
 between the battery 
and the DC-UPS and requires a fully charged (min. 24h) battery. 
 
 
Fig. 9-1   
Buffer time vs. output current with the battery modules UZK12.071 and UZK12.261
 
Buffer Current
5
15
2
4
6
8
10A
20
10
25 30 35
45 50
40
55 60 65 70 75 80 85
Buffer Time (Minutes)
UZK12.071 typ.
UZK12
.261 ty
p.
12V 7Ah battery
12V 26
Ah batt
ery
120
150
210 240
300
  Min.
180
270
90
UZK12.261 typ.
UZK12.071 typ.
90
 
 
 
The battery capacity is usually specified in amp-hours (Ah) for a 20h discharging event. The battery discharge is non-
linear (due to the battery chemistry). The higher the discharging current, the lower the appropriable battery capacity. 
The magnitude of the reduction depends on the discharging current as well as on the type of battery. High current 
battery types can have up to 50% longer buffer times compared to regular batteries when batteries will be 
discharged in less than 1 hour. 
High discharging currents do not necessarily mean high power losses as the appropriable battery capacity is reduced 
with such currents. When the battery begins to recharge after a discharging event, the process is completed much 
faster since only the energy which was taken out of the battery needs to be “refilled”. 
For this reason, the buffer time cannot be calculated using the Ah capacity value. The equation “I x t” = capacity in 
Ah generally leads to incorrect results when the discharging current is higher than C20 (discharging current for 20h). 
The battery datasheet needs to be studied and a determination of the expected buffer time can be made according 
to the following example: 
 
June. 2010 / Rev. 1.3  DS-UB10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 