Puls UZK12.071 Battery Guia De Especificação

Página de 9
 
 
UZK12.071, UZO12.07
 
 
U-Series 
B
ATTERY 
M
ODULE 
12V,
 
7AH 
 
 
17.  R
ECOMMENDATIONS FOR A 
L
ONG 
B
ATTERY 
L
IFE
 
 
Temperature: 
The temperature has the most impact on the service life. The hotter the temperature, the earlier the wear-out phase 
of the battery begins. The wear-out results in a degradation of battery capacity. Place the battery module in a cool 
location, E.g. near the bottom of the control cabinet. Do not place the battery module near heat generating devices. 
Do not overcharge batteries! 
 
Fig. 17-1   Service life vs. ambient temperature, typ. 
 
 
20°C
10
30°C
35°C
40°C
45°C
8
6
4
2
Ambient Temperature
25°C
1
3
5
7
9
Service Life in Years
Design Life
of Battery
A:  3-5 Years
B:  6-9 Years
C:  10-12 Years
A
B
C
 
 
 
Number of discharge cycles and depth of discharge: 
Do not discharge batteries more than necessary. Set buffer time limiter to the required buffer time. The number, as 
well as the depth of discharging cycles is limited. A replacement of the battery might be necessary earlier. 
When choosing the battery capacity, always try to get the next higher capacity than required. The depth of discharge 
reduces the service life of the battery and limits the number of cycles. 
 
Fig. 17-2   Battery degradation vs. discharging 
cycles, typ. 
 
 
0
120%
100%
40%
20%
Number of Discharging Cycles
200
60%
80%
Cell Capacity
Depth of
discharge
A:  100%
B:   50%
C:   30%
400
600
800
1000 1200
A
B
C
 
 
 
 
Jul. 2014 / Rev. 2.0 DS-UZK12.071 
All parameters are specified at, 25°C ambient temperature unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
8/9