Puls YR2.DIODE Redundancy Module Guia De Especificação

Página de 18
 
 
YR2.DIODE
 
 
Y-Series 
DC12-48V,
 
20A,
 
D
UAL 
R
EDUNDANCY 
M
ODULE
 
 
 
19.  A
PPLICATION 
N
OTES
 
19.1.  R
ECOMMENDATIONS FOR 
R
EDUNDANCY
 
Recommendations for the configuration of redundant power systems: 
• 
Use separate input fuses for each power supply. 
• 
Use three-phase power supplies to gain functional safety if one phase fails. 
• 
When single-phase power supplies are utilized connect them to different phases or mains circuits if possible. 
• 
Set the power supply in “Parallel-Use” mode if this feature is available 
• 
It is desirable to set the output voltages of all power supplies to the same value. 
 
19.2.  I
NDUCTIVE AND 
C
APACITIVE 
L
OADS
 
The unit is designed to supply any kind of loads, including unlimited capacitive and inductive loads. 
 
19.3.  E
XAMPLE
:
 
1+1
 
R
EDUNDANCY UP TO 
10A 
1+1 Redundancy up to 10A requires two 10A power supplies and one YR2.DIODE redundancy module. 
 
Fig. 19-1   Wiring diagram, 1+1 Redundancy, 10A output current 
 
L   N  PE
+ +
- -
QS10.241
Power
Supply
Adj
Overload
DCok
24V,10A
Failure
Monitor
10A
Load
optional
I
I
L
N
PE
L   N  PE
+ +
- -
QS10.241
Power
Supply
Adj
Overload
DCok
24V,10A
YR2.Diode
Redundancy
Module
+  
-
OUT
-
IN 1
-
IN 2
 
Note: Use separate mains systems for each power supply whenever it is possible
 
 
May 2010 / Rev. 1.2 DS-YR2.DIODE-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 
www.pulspower.com   Phone +49 89 9278 0    Germany 
14/18