19.6. E
XAMPLE
:
R
EDUNDANCY FOR
C
ONTROLS
The example shows a cost effective solution to get redundant power for a PLC or controller system.
In many cases, two power supplies are used; one for the demanding loads and another one for the controls and
sensitive loads. The power supply for the demanding loads can be used as a redundant source to supply the controls.
sensitive loads. The power supply for the demanding loads can be used as a redundant source to supply the controls.
Traditional approach:
Load
PS1
PLC
PS2
Improved approach:
Load
PLC
PS1
PS2
YR2
Fig. 19-4 Wiring diagram, redundancy for sensitive loads
Sensitive
Load
e.g.
Controller
optional
L N PE
+ +
- -
QS5.241
Power
Supply
Adj
Overload
DCok
24V,
5A
I
I
I
L1
L2
L2
PE
L3
I
N
Heavy
Loads
e.g. Motors
L1 L2 L3 PE
+ +
- -
QT20.241
Power
Supply
Adj
Overload
DCok
24V,20A
YR2.Diode
Redundancy
Module
+
-
OUT
+
-
IN 1
+
-
IN 2
Failure
Monitor
Note: Use separate mains systems for each power supply whenever it is possible
May 2010 / Rev. 1.2 DS-YR2.DIODE-EN