Puls YR2.DIODE Redundancy Module Guia De Especificação
YR2.DIODE
Y-Series
DC12-48V,
20A,
D
UAL
R
EDUNDANCY
M
ODULE
19. A
PPLICATION
N
OTES
19.1. R
ECOMMENDATIONS FOR
R
EDUNDANCY
Recommendations for the configuration of redundant power systems:
•
Use separate input fuses for each power supply.
•
Use three-phase power supplies to gain functional safety if one phase fails.
•
When single-phase power supplies are utilized connect them to different phases or mains circuits if possible.
•
Set the power supply in “Parallel-Use” mode if this feature is available
•
It is desirable to set the output voltages of all power supplies to the same value.
19.2. I
NDUCTIVE AND
C
APACITIVE
L
OADS
The unit is designed to supply any kind of loads, including unlimited capacitive and inductive loads.
19.3. E
XAMPLE
:
1+1
R
EDUNDANCY UP TO
10A
1+1 Redundancy up to 10A requires two 10A power supplies and one YR2.DIODE redundancy module.
Fig. 19-1 Wiring diagram, 1+1 Redundancy, 10A output current
L N PE
+ +
- -
QS10.241
Power
Supply
Adj
Overload
DCok
24V,10A
Failure
Monitor
10A
Load
optional
I
I
L
N
PE
L N PE
+ +
- -
QS10.241
Power
Supply
Adj
Overload
DCok
24V,10A
YR2.Diode
Redundancy
Module
+
-
OUT
+
-
IN 1
+
-
IN 2
Note: Use separate mains systems for each power supply whenever it is possible
May 2010 / Rev. 1.2 DS-YR2.DIODE-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
14/18