Puls YRM2.DIODE Redundancy Module Guia De Especificação

Página de 18
 
 
YRM2.DIODE
 
 
Y-Series 
DC24-48V,
 
20A,
 
D
UAL 
R
EDUNDANCY 
M
ODULE
 
 
 
20.4.  E
XAMPLE
:
 
N+1
 
R
EDUNDANCY UP TO 
30A 
N+1 Redundancy up to 30A requires four 10A power supplies and two YRM2.DIODE redundancy modules. 
 
Fig. 20-2   Wiring diagram, n+1 Redundancy, 30A output current 
 
optional
I
I
L
N
PE
I
L   N  PE
10A
Power Supply
+   +
-  -
24V, 10A
L   N  PE
10A
Power Supply
+   +
-  -
24V, 10A
L   N  PE
10A
Power Supply
+   +
-  -
24V, 10A
Failure
Monitor
30A
Load
YRM2.DIODE
+  
-
OUT
 -
IN 1
+  
-
IN 2 IN 1 IN 2
YRM2.DIODE
+  
-
OUT
 -
IN 1
+  
-
IN 2 IN 1 IN 2
L   N  PE
10A
Power Supply
+   +
-  -
24V, 10A
I
optional
 
Note: Use separate mains systems for each power supply whenever it is possible
 
 
20.5.  E
XAMPLE
:
 
B
ATTERY 
B
ACK
-
UP
 
A battery back-up with 10A requires one 10A power supply and one YRM2.DIODE redundancy module. 
Please note: 
Set output voltage of power supply to 26.5Vdc minimum to ensure, that the load current is delivered from the power 
supply and not from charger (battery). Use a fuse between battery and YRM2.DIODE! 
 
Fig. 20-3   Wiring diagram, 10A Battery back-up 
 
optional
L
N
PE
24V Battery
I
Battery
Charger
+
-
Failure
Monitor
10A
Load
L   N  PE
10A
Power Supply
+   +
-  -
24V, 10A
YRM2.DIODE
+  
-
OUT
 -
IN 1
+  
-
IN 2 IN 1 IN 2
 
May 2010 / Rev. 1.2 DS-YRM2.DIODE-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 
www.pulspower.com   Phone +49 89 9278 0    Germany 
15/18