Puls CS10.241 Power Supply Guia De Especificação
CS10.241, CS10.241-S1
C–Series
24V, 10A, S
INGLE
P
HASE
I
NPUT
August 2006 / Rev. 1.1 DS-CS10.241-EN / All parameters are specified at 24V, 10A, 230Vac and 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/20
15. E
NVIRONMENT
Operational temperature
-25°C to +70°C (-13°F to 158°F)
reduce output power according
Fig. 15-1
Output de-rating
3.2W/°C
45-60°C (113°F to 140°F)
6W/°C
60-70°C (140°F to 158°F)
Storage temperature
-40 to +85°C (-40°F to 185°F)
storage and transportation
Humidity
5 to 95% r.H.
IEC 60068-2-30
Do not energize while condensation is present
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
2 hours / axis
IEC 60068-2-6
Shock
30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude
0 to 6000m (0 to 20 000ft)
Reduce output power or ambient
temperature above 2000m sea level.
temperature above 2000m sea level.
Output de-rating (for altitude)
15W/1000m or 5°C/1000m
above 2000m (6500ft), see
Fig. 15-2
Over-voltage
category
III
EN
50178, altitudes up to 2000m
II
Altitudes from 2000m to 6000m
Degree of pollution
2
EN 50178, not conductive
Fig. 15-1 Output current vs. ambient temp.,
Fig. 15-2 Output current vs. altitude, 24V
0
-25
0
20
40
70°C
2
4
6
8
10
12A
60
Ambient Temperature
continuous
short
term
Allowable Output
Current at 24V
Current at 24V
0
0
2000
4000
6000m
2
4
6
8
10
12A
Altitude
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
C... Tamb < 40°C
C
B
A
short term
Allowable Output
Current at 24V
Current at 24V
The ambient temperature is defined 2cm below the unit.
16. P
ROTECTION
F
EATURES
Output
protection
Electronically protected against overload, no-load and short-circuits
Output over-voltage protection
typ. 35Vdc
max. 39Vdc
max. 39Vdc
In case of an internal power supply defect, a redundant
circuitry limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
circuitry limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Output over-current protection electronically
limited see
Fig. 8-1
Degree of protection
IP 20
EN/IEC 60529
Penetration protection
> 3.5mm
e.g. screws, small parts
Over-temperature
protection
yes
output shut-down with automatic restart
Input transient protection
MOV
Metal Oxide Varistor
Internal input fuse
T6.3A H.B.C.
not user replaceable
Note: In case of a protection event, audible noise may occur.