August 2006 / Rev. 1.1  DS-CS10.241-EN / All parameters are specified at 24V, 10A, 230Vac and 25°C ambient unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
9/20 
 
14. EMC 
 
The CE mark is in conformance with EMC guideline 89/336/EEC and 93/68/EEC and the low-voltage directive (LVD) 
73/23/EWG. A detailed EMC Report is available on request. 
 
 
EMC Immunity 
EN 61000-6-2, EN 61000-6-1 
Generic standards 
 
Electrostatic discharge  
EN 61000-4-2 
Contact discharge 
Air discharge 
8kV 
15kV 
Criterion A 
Criterion A 
  Electromagnetic RF field 
EN 61000-4-3 80MHz-1GHz 
10V/m 
Criterion 
 
Fast transients (Burst) 
EN 61000-4-4 
Input lines 
Output lines 
4kV 
2kV 
Criterion A 
Criterion A 
 
Surge voltage on input 
EN 61000-4-5 
L Æ N 
N / L Æ PE 
2kV  
4kV 
Criterion A 
Criterion A 
 
Surge voltage on output 
EN 61000-4-5 
+ Æ - 
+ / - Æ PE 
500V 
500V 
Criterion A 
Criterion A 
  Conducted disturbance 
EN 61000-4-6 
0,15-80MHz 
10V 
Criterion A 
 
Mains voltage dips 
EN 61000-4-11 
0% of 100Vac
 
40% of 100Vac 
70% of 100Vac  
0% of 200Vac
 
40% of 200Vac 
70% of 200Vac 
0Vac, 20ms 
40Vac, 200ms 
70Vac, 500ms 
0Vac, 20ms 
80Vac, 200ms 
140Vac, 500ms 
Criterion A 
Criterion C 
Criterion C 
Criterion A 
Criterion C 
Criterion C 
  Voltage interruptions 
EN 61000-4-11 
 
0Vac, 5000ms 
Criterion C 
  Input voltage swells 
PULS internal standard 
 
300Vac, 500ms 
Criterion A 
 
Powerful transients 
VDE 0160 
over entire load 
range 
750V, 1.3ms 
Criterion A 
Criterions: 
A:  Power supply shows normal operation behavior within the defined limits.  
C:  Temporary loss of function is possible. Power supply might shut-down and restarts by itself. No damages or hazards for the 
power supply occur. 
 
 
  Switching frequency 
85kHz to 110kHz 
input voltage dependent