Puls CS10.241 Power Supply Guia De Especificação
CS10.241, CS10.241-S1
C–Series
24V, 10A, S
INGLE
P
HASE
I
NPUT
August 2006 / Rev. 1.1 DS-CS10.241-EN / All parameters are specified at 24V, 10A, 230Vac and 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3/20
5. AC-I
NPUT
AC
input
nom.
AC 100-120V /
200-240V
200-240V
auto-select input, TN-, TT-, IT-Mains, see
Fig. 5-1
AC input range
90-132Vac
100-120V range, continuous operation
180-264Vac
200-240V range, continuous operation
85-90Vac
Short term or with output derating
264-300Vac <
0.5s
Input
frequency
nom.
50 – 60Hz
±6%
AC 100V
AC 120V
AC 230V
Input
current
typ.
4.34A
3.73A
2.23A
at 24V, 10A see
Fig. 5-3
Power
factor
*)
typ.
0.61
0.59
0.51
at 24V, 10A see
Fig. 5-1
Crest factor **)
typ.
2,61
2,83
3,3
at 24V, 10A
Start-up
delay
typ.
700ms 800ms 850ms
see
Fig. 5-2
Rise
time
typ.
35ms
35ms
35ms
0mF, 24V, 10A, see
Fig. 5-2
typ.
75ms
75ms
75ms
10mF, 24V, 10A, see
Fig. 5-2
Turn-on
overshoot
max.
100mV 100mV 100mV
see
Fig. 5-2
Turn-on
voltage
typ.
80Vac
80Vac
N / A
steady-state value, see
Fig. 5-1
Shut-down
voltage
typ.
75Vac
75Vac
N / A
steady-state value, see
Fig. 5-1
*)
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to the RMS value of the input current waveform
Fig. 5-1 Input voltage range
Fig. 5-2 Turn-on behavior, definitions
Tur
n
-on
90V
Rated input ranges
V
IN
P
OUT
264Vac
180V
S
hut
-down
132V
no
harm
from
132 to
180V
Range
100-
120V
Range
200-
240V
Start-up
delay
Rise
Time
Ov
ershoot
- 5%
Output
Voltage
Voltage
Intput
Voltage
Voltage
Fig. 5-3 Input current vs. output load
Fig. 5-4 Power Factor vs. output load
12A
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6A
Input
Current, typ.
Current, typ.
10 11
Output Current
230Va
c
120
Vac
100
Vac
12A
2
3
4
6
8
0.35
0.4
10
Output Current
5
7
9
11
0.45
0.5
0.55
0.6
0.65
Power Factor, typ.
230Vac
120Vac
100Vac