Puls QS5.241 Power Supply Guia De Especificação

Página de 26
 
 
QS5.241, QS5.241-A1
 
 
Q-Series 
24V,
 
5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
16.  P
ROTECTION 
F
EATURES
 
 
Output protection 
Electronically protected against overload, no-load and short-circuits 
*)
 
Output over-voltage protection typ. 
32Vdc 
max. 36Vdc 
In case of an internal power supply defect, a redundant 
circuit limits the maximum output voltage. The output 
shuts down and automatically attempts to restart. 
Degree of protection 
IP 20 
EN/IEC 60529 
Penetration protection 
> 3.5mm 
e.g. screws, small parts 
Over-temperature protection 
yes 
Output shut-down with automatic restart 
Input transient protection 
MOV (Metal Oxide Varistor) 
Internal input fuse 
T3.15A H.B.C. 
not user replaceable 
*)   In case of a protection event, audible noise may occur. 
 
17.  S
AFETY 
F
EATURES
 
 
Input / output separation 
*)
 SELV 
IEC/EN 
60950-1 
 
PELV 
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41 
Class of protection 
PE (Protective Earth) connection required 
Isolation resistance 
> 5MOhm 
input to output, 500Vdc  
PE resistance 
< 0.1Ohm 
Touch current (leakage current) 
typ. 0.11mA / 0.28mA 
100Vac, 50Hz, TN-,TT-mains / IT-mains 
 
typ. 0.16mA / 0.4mA 
120Vac, 60Hz, TN-,TT-mains / IT-mains 
 
typ. 0.27mA / 0.68mA 
230Vac, 50Hz, TN-,TT-mains / IT-mains 
 
< 0.14mA / 0.33mA 
110Vac, 50Hz, TN-,TT-mains / IT-mains 
 
< 0.22mA / 0.49mA 
132Vac, 60Hz, TN-,TT-mains / IT-mains 
 
< 0.40mA / 0.88mA 
264Vac, 50Hz, TN-,TT-mains / IT-mains 
*)   double or reinforced insulation 
 
18.  D
IELECTRIC 
S
TRENGTH
 
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by 
the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the 
voltage with a slow ramp (2s up and 2s down). Connect all input-terminals together as well as all output poles before 
conducting the test. When testing, set the cut-off current settings to the value in the table below. 
 
Fig. 18-1   Dielectric strength 
 
 
 
A B  C  D 
Type test 
60s 
2500Vac 
3000Vac 
500Vac 
500Vac 
Factory test 
5s 
2500Vac 
2500Vac 
500Vac 
500Vac 
Field test 
5s 
2000Vac 
2000Vac 
500Vac 
500Vac 
Cut-off current setting  > 10mA 
> 10mA 
> 20mA 
> 1mA 
 
A
D
C
B
B
N
L
Input
DC-ok
Earth, PE
Output
 -
+
 
 
 
To fulfil the PELV requirements according to EN60204-1 § 6.4.1, we 
recommend that either the + pole, the – pole or any other part of 
the output circuit shall be connected to the protective earth 
system. This helps to avoid situations in which a load starts 
unexpectedly or can not be switched off when unnoticed earth 
faults occur. 
Mar. 2013 / Rev. 2.2 DS-QS5.241-EN 
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
15/26