14.  EMC 
The power supply is suitable for applications in industrial environment as well as in residential, commercial and light 
industry environment without any restrictions.  
The CE mark indicates conformance with the EMC directive 2004/108/EC, the low-voltage directive (LVD) 2006/95/EC 
and the RoHS directive 2011/65/EC. A detailed EMC report is available on request. 
 
EMC Immunity 
According generic standards: EN 61000-6-1 and EN 61000-6-2 
Electrostatic discharge  
EN 61000-4-2 
contact discharge 
air discharge 
8kV 
15kV 
Criterion A 
Criterion A 
Electromagnetic RF field 
EN 61000-4-3 
80MHz-2.7GHz 
10V/m 
Criterion A 
Fast transients (Burst) EN 
61000-4-4 
input 
lines 
output lines 
DC-OK signal (coupling clamp) 
4kV 
2kV 
1kV 
Criterion A 
Criterion A 
Criterion A 
Surge voltage on input 
EN 61000-4-5 
L Æ N 
L Æ PE, N Æ PE 
2kV 
4kV 
Criterion A 
Criterion A 
Surge voltage on output 
EN 61000-4-5 
+ Æ - 
+ / - Æ PE 
1kV 
1kV 
Criterion A 
Criterion A 
Surge voltage on DC-OK 
EN 61000-4-5 
DC-OK signal Æ PE 
1kV 
Criterion A 
Conducted disturbance 
EN 61000-4-6 0.15-80MHz 
10V 
Criterion 
Mains voltage dips 
EN 61000-4-11 
0% of 100Vac 
40% of 100Vac 
70% of 100Vac 
0% of 200Vac
 
40% of 200Vac 
70% of 200Vac 
0Vac, 20ms 
40Vac, 200ms 
70Vac, 500ms 
0Vac, 20ms 
80Vac, 200ms 
140Vac, 500ms 
Criterion A 
Criterion C  
Criterion A 
Criterion A 
Criterion A 
Criterion A 
Voltage interruptions 
EN 61000-4-11 
0% of 200Vac (=0V) 
5000ms 
Criterion C 
Voltage sags 
SEMI F47 0706 
dips on the input voltage according to SEMI F47 standard 
 
 
80% of 120Vac (96Vac) 
70% of 120Vac  (84Vac)
 
50% of 120Vac (60Vac) 
1000ms 
500ms 
200ms 
Criterion A 
Criterion A 
Criterion A 
Powerful transients 
VDE 0160 
over entire load range 
750V, 1.3ms 
Criterion A 
Criterions: 
A:    Power supply shows normal operation behavior within the defined limits.  
C:    Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply 
will occur. 
 
EMC Emission 
According generic standards: EN 61000-6-3 and EN 61000-6-4 
Conducted emission  
input lines 
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 
Class B 
Conducted emission  
output lines **) 
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 
limits for DC power port 
according EN 61000-6-3 fulfilled 
Radiated emission 
EN 55011, EN 55022 
Class B 
Harmonic input current 
EN 61000-3-2 
fulfilled for class A equipment 
Voltage fluctuations, flicker 
EN 61000-3-3 
fulfilled *) 
This device complies with FCC Part 15 rules. 
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 
*)   tested with constant current loads, non pulsing 
**)  for information only, not mandatory for EN 61000-6-3 
Mar. 2013 / Rev. 2.2 DS-QS5.241-EN 
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 